Good quality Medium Voltage Load Switch - PGS Series Outdoor High Voltage SF6 Load Break Switch – Ghorit Detail:
PGS-630A pole mounted load break switch is used for breaking rated voltage 12/24/40.5kV, rated current 630A, 50/60Hz power distribution system, closing load current and over load current of power system, it could separate automatically track sections of power distribution which faults occur. The switch is matched with electronic controller which is with the latest technology. The switch has manual, motor, remote operation modes. The electronic controller would be installed inside the stainless steel box, so it could be used in various climate conditions. Besides that, the wire/wireless modem installed inside control box could achieve remote monitoring and controlling. It’s easy and convenient for installation the switch on pole, and that could reduce the execution cost.
Environmental Conditions
♦ Air temperature: -40℃~+50℃;
♦ Relative humidity: 110%
♦ Altitude ≤3000m.
♦ Wind pressure ≤700pa (equivalent to wind speed 34m/s).
♦ Seismic intensity: 8 degree.
♦ Installation site: No fire disaster, explosion danger, chemical corrosion and frequent strenuous vibration places).
♦ Pollution grade: Ⅲ class, Ⅳclass.
Type descriptions
MPP types

♦ Porcelain bushing-molded cable outlet

♦ Rubber split bushing-molded cable outlet

♦ Integrative rubber bushing-wiring terminal outlet

♦ with surge arrestor
♦ Porcelain bushing-wiring terminal outlet
Technical Parameter
| Products Type | PGS-12 |
PGS-24 |
PGS-40.5 |
| Basic Ratings | |||
| Maximum system voltage | 15KV |
25.8KV |
40.5KV |
| Rated continuous current | 630A | 630A | 630A |
| Rated frequency | 50/60Hz |
50/60Hz |
50/60Hz |
| Short time withstand current | 20KA/4s |
25KA/1s |
20KA/1s |
| Making and Breaking Capacity | |||
| Mainly active load current | 630A | 630A | 630A |
| Number of load-break operations | 400times |
400times |
400times |
| Short-circuit making current (peak) | 50KA | 50KA | 50KA |
| Number of making operations | 5 times |
5 times |
5 times |
| Cable charging current | 25A | 25A | 25A |
| Line charging current | 1.5A | 1.5A | 2A |
| Closed loop circuit current | 630A | 630A | 630A |
| Rated no-load transformer breaking current | 22A | 22A | 22A |
| Power Frequency Withstand Current Test | |||
| 10s(wet test),phase- phase-earth, across open contacts | 45KV | 50KV | 70KV |
| 1min(dry test), earth, phase to earth | 50KV | 60KV | 95KV |
| 1min(dry test), across open contacts | 50KV | 60KV | 110KV |
| Impulse Withstand Current Test( 1.2 x 50 µs ) | |||
| Phase-to-phase, phase-to-earth | 85KV | 150KV | 195KV |
| Across open contacts | 95KV | 150KV | 215KV |
| Other Ratings & Specifications | |||
| Internal arc test | 20kA /0.1 s | 20kA /0.1 s | 20kA /0.1 s |
| Arc extinction medium | SF 6 Gas | SF 6 Gas | SF 6 Gas |
| Insulation medium | SF 6 Gas | SF 6 Gas | SF 6 Gas |
| Creepage distance (porcelain) | 550mm | 840mm | 1055mm |
| Creepage distance (silicon) | 610mm | 900mm | 1250mm |
| IP level | 54 | 54 | 54 |
| Operation Performance | |||
| Closing/opening time | <1sec | <1sec | <1sec |
| Mechanical operations (guaranteed) | 10000times | 10000times | 10000times |
| Operating temperature (*manual type) | -25(-40)~70℃ | -25(-40)~70℃ | -25(-40)~70℃ |
| Gas Pressure | |||
| Rated working pressure (kg/cm2 G, at 20°C) | 0.7 | 1.0 | 1.0 |
| Explosion-protection equipment action pressure (kg/cm2 G) | 4~6 | 4~6 | 4~6 |
| Minimum working pressure (kg/cm2 G) | 0.05 | 0.0 | 0.0 |
| Gas leakage rate (cc/ s) | ≤1% | ≤1% | ≤1% |
Overall Dimensions


| Dimension(mm) | InstallationDimension(mm) | Packing size(mm) | Creep distance ofbushing(mm) | |||
| A | B | C | Length × Width | Length×Width×high | ||
| 10KV | 225 | 435 | 500 | 500×390 | 1100×900×700 | 556 |
| 24KV | 300 | 435 | 500 | 500×390 | 1300×1100×700 | 840 |
| 40.5KV | 350 | 435 | 500 | 700×390 | 1400×1200×700 | 1250 |
Product detail pictures:

Related Product Guide:
Our firm sticks on the theory of "Quality will be the life in the enterprise, and status could be the soul of it" for Good quality Medium Voltage Load Switch - PGS Series Outdoor High Voltage SF6 Load Break Switch – Ghorit, The product will supply to all over the world, such as: Manchester, Lyon, Slovenia, With well educated, innovative and energetic staff, we are responsible for all elements of research, design, manufacture, sale and distribution. By studying and developing new techniques, we are not only following but also leading fashion industry. We listen attentively to the feedback from our customers and provide instant replies. You will instantly feel our professional and attentive service.
By Miranda from California - 2017.12.31 14:53
Company director has very rich management experience and strict attitude, sales staff are warm and cheerful, technical staff are professional and responsible,so we have no worry about product,a nice manufacturer.
By Ivy from France - 2018.06.26 19:27
-
Hot Sale for Side Type Vcb - GHV-12G/630 Circu...
-
China wholesale Sf6 Gas Load Break Switch - GH...
-
OEM manufacturer 0.2 Class Electric Transformer...
-
Manufacturer for China Supplier Vacuum Interrup...
-
Cheap PriceList for High Voltage Ac Load Switch...
-
2020 Good Quality High Voltage Switchgear - HC...