Hot sale Indoor High Voltage Vacuum Breaker - VS1-12 Series Indoor High Voltage Vacuum Circuit Breaker – Ghorit Detail:
VS1-12 indoor HV vacuum circuit breaker is a 3-phase AC 50Hz 12kV indoor switch equipment.
♦ Installation way: withdrawable type, fixed type, side mounted type;
♦ Operating mechanism: spring ope rating mechanism, permanent magnetic operating mechanism;
♦ Pole type: assembled pole, embedded pole;
♦ Application: switchgear KYN28-12, XGN-12.
♦ Secondary plug: 58pins, 64pins.


Product Standards
♦ IEC62271-100 High Voltage Switchgear and Controlgear Part 100: AC Circuit-breakers
♦ GB1984 High Voltage AC Circuit-breakers
♦ GB/T11022 Common Specifications for High-voltage Switchgear and Controlgear Standards
♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers
♦ DL/T402 Specification of High-voltage AC Circuit-breakers
Environmental Conditions
♦ Ambient temperature: -15°C~+40°C;
♦ Altitude: <1000m;
♦ Relative humidity: daily average <95%, monthly average <90%;
♦ Earthquake intensity: <8 level;
♦ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense vibration.
Main Technical Parameters
| No |
Item |
Unit |
Value |
| 1 | Rated voltage | kV |
12 |
| 2 | 1 min power frequency withstand voltage |
42 |
|
| 3 | Rated lightning impulse withstand voltage |
75 |
|
| 4 | Rated frequency | Hz |
50 |
| 5 | Rated current | A |
630, 1250, 1600, 2000, 2500, 3150, 4000 |
| 6 | Rated short circuit breaking current | kA |
20, 25, 31.5, 40 |
| - | Rated short time withstand current |
20, 25, 31.5, 40 |
|
| fa | Rated short circuit duration | s |
4 |
| 9 | Rated peak value withstand current |
kA |
50, 63, 80, 100 |
| 10 | Rated short circuit making current |
50, 63, 80, 100 |
|
| 11 | Secondary circuit power frequency withstand voltage (1min) | V |
2000 |
| 12 | Rated single / back-to-back capacitor bank breaking current | A |
630/400 (800/400 for 40kA and 50kA) |
|
No |
Item |
Unit |
Value |
|
13 |
Rated capacitor bank closing inrush current | A |
12.5 |
|
14 |
Opening time (rated voltage) |
ms |
20-50 |
|
15 |
Closing time (rated voltage) |
ms |
35-70 |
|
16 |
Mechanical life |
Times |
10000 |
|
17 |
Rated current breaking number |
Times |
10000 |
|
18 |
Rated short circuit current breaking number |
Times |
50 (30 for 40kA; 20 for 50kA) |
|
19 |
Moving and fixed contacts cumulative allowed wear thickness | mm |
3 |
| 20 | Rated closing operating voltage | V |
AC/DC110/220 |
| 21 | Rated opening operating voltage | ||
| 22 | Rated voltage of energy storage motor |
W |
70 (80 ror 40kA and 50kA) |
| 23 | Rated power of energy storage motor | ||
| 24 | Energy storage time | s |
<10 |
| 25 | Clearance between open contacts | mm |
11±1 |
| 26 | Over travel | mm |
3.5±0.5 |
| 27 | Contact closing bounce time | ms |
<2 (<3 for 40kA and 50kA) |
| 28 | Three phase opening and closing asynchronism | ms |
<2 |
| 29 | Average opening speed |
m/s |
0.9-1.2 |
| 30 | Average closing speed |
m/s |
0.5-0.8 |
| 31 | Main conductive circuit resistance | uQ |
<60 (630A) <50(1250A) <35(1600-2000A) <25(above 2500A) |
| 32 | Closing contact pressure of the contacts | N |
2000±200 (20kA) 2400±200 (25kA) 3100±200 (31.5kA) 4250±250 (40kA) 6500±500 (50kA) |
| 33 | Rated operating sequence |
O-0.3s-CO-180s-CO O-180s-CO-180s-CO (50kA) |
Note: when current is 4000A or 5000A, need forced air cooling.
General Structure Drawing and Installation Size (unit: mm)
♦ Draw out type

|
Cabinet width |
Rated current (A) |
Rated short circuit breaking current (kA) |
P | H |
A |
B |
C |
D |
E | F |
G |
J |
K |
L |
M |
N |
R |
S |
T |
| 650 | 630 |
20 〜31.5 |
150 | 275 | 490 | 502 | 492 |
500 |
433 | 626 |
035 |
280 | 598 | 76 | 78 | 637 | 508 | 202 | 40 |
| 650 | 1250 |
20 〜31.5 |
150 | 275 | 490 | 502 | 492 |
500 |
433 | 626 |
049 |
280 | 598 | 76 | 78 | 637 | 508 | 202 | 40 |
| 800 | 630 |
20 〜31.5 |
210 | 275 | 638 | 652 | 640 |
650 |
433 | 626 |
035 |
280 | 598 | 76 | 78 | 637 | 508 | 277 | 40 |
| 800 | 1250 |
20-40 |
210 | 275 | 638 | 652 | 640 |
650 |
433 | 626 |
049 |
280 | 598 | 76 | 78 | 637 | 508 | 277 | 40 |
| 800 | 1600 |
31.5〜40 |
210 | 275 | 638 | 652 | 640 |
650 |
433 | 626 | 055 | 280 | 598 | 76 | 78 | 637 | 508 | 277 | 40 |
| 1000 | 630 |
20 〜31.5 |
275 | 275 | 838 | 852 | 838 |
850 |
433 | 626 |
035 |
280 | 598 | 76 | 78 | 637 | 508 | 377 | 40 |
| 1000 | 1250 |
20 〜40 |
275 | 275 | 838 | 852 | 838 |
850 |
433 | 626 |
049 |
280 | 598 | 76 | 78 | 637 | 508 | 377 | 40 |
| 1000 | 1600 |
31.5-40 |
275 | 275 | 838 | 852 | 838 |
850 |
433 | 626 |
055 |
280 | 598 | 76 | 78 | 637 | 508 | 377 | 40 |
| 1000 | 1600-200 |
31.5 〜40 |
275 | 310 | 838 | 852 | 838 |
850 |
361 | 680 |
079 |
295 | 586 | 77 | 88 | 698 | 536 | 377 |
0 |
| 1000 | 2500〜200 |
31.5 〜40 |
275 | 310 | 838 | 852 | 838 |
850 |
361 | 680 |
0109 |
295 | 586 | 77 | 88 | 698 | 536 | 377 |
0 |
♦ Fixed type

|
Cabinet width |
Ra»a current (A) |
P |
H |
A |
C |
E |
G1 |
J |
K |
L |
|
650 |
630-1600 |
150 |
275 |
385 |
440 |
580 |
I |
237 |
455 |
395 |
|
800 |
630-1600 |
210 |
275 |
520 |
588 |
580 |
II |
237 |
455 |
410 |
|
1000 |
630~1600 |
275 |
275 |
720 |
770 |
580 |
II |
237 |
455 |
410 |
|
1000 |
1600~5000 |
275 |
310 |
720 |
770 |
632 |
III |
252 |
465 |
440 |
♦ Side mounted type

Product detail pictures:





Related Product Guide:
"Sincerity, Innovation, Rigorousness, and Efficiency" could be the persistent conception of our enterprise to the long-term to produce together with clients for mutual reciprocity and mutual profit for Hot sale Indoor High Voltage Vacuum Breaker - VS1-12 Series Indoor High Voltage Vacuum Circuit Breaker – Ghorit, The product will supply to all over the world, such as: Gambia, Peru, Luxemburg, We strongly believe that technology and service is our base today and quality will create our reliable walls of future. Only we have better and better quality , could we achieve our customers and ourselves, too. Welcome customers all over the word to contact us for getting further business and reliable relationships. We are always here working for your demands whenever you need.
By Candance from Ukraine - 2018.12.28 15:18
The after-sale warranty service is timely and thoughtful, encounter problems can be resolved very quickly, we feel reliable and secure.
By Carey from Cannes - 2017.04.08 14:55
-
Factory Outlets High Voltage Outdoor Vacuum Cir...
-
Leading Manufacturer for Vs1-12 Indoor Hv Vacuu...
-
OEM Manufacturer Recloser Breaker - GHV-12G/63...
-
Original Factory 20kv Potential Instrument Tran...
-
Trending Products Ground Operated Switch - FZR...
-
High definition Circuit Breaker 15kv - GHV-12G...