Wholesale Parts Of Vacuum Circuit Breaker - VSG-24 Series Indoor High Voltage Vacuum Circuit Breaker – Ghorit Detail:
VSG-24 series lateral type indoor high voltage vacuum circuit breaker applies to three-phase AC 50(60)Hz 24KV power system, which can be used for switching load current, overload current and fault current in industrial and mining enterprises, power plant, transformer substation and suitable for frequent operation occasions It also widely applies to projects, as power plant, power system, petrifaction, metallurgy, metro, airdrome, building, etc.
Environmental Conditions
♦ Ambient temperature: -10°C-+40°C;
♦ Altitude: <1000m;
♦ Relative humidity: daily average <95%, monthly average <90%;
♦ Earthquake intensity: <8 level;
♦ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense vibration.
Main Technical Parameters
| No |
Item |
Unit |
Value |
| 1 | Rated voltage | kV |
24 |
| 2 | 1 min power frequency withstand voltage |
65 |
|
| 3 | Rated lightning impulse withstand voltage |
125 |
|
| 4 | Rated frequency | Hz |
50 |
| 5 | Rated current | A |
630, 1250 |
| 6 | Rated short circuit breaking current |
kA |
25, 31.5 |
| 7 | Rated short circuit making current (peak) |
63, 80 |
|
| 8 | Rated short time withstand current |
25, 31.5 |
|
| 9 | Rated peak value withstand current |
63, 80 |
|
| 10 | Rated short circuit duration | s |
4 |
| 11 | Rated operating sequence |
O-0.3s-CO-180s-CO |
|
| 12 | Secondary circuit power frequency withstand voltage (1min) |
V |
2000 |
| 13 | Rated sing e/back-to-back capacitor bank breaking current |
kA |
630/400 |
| Breaking time | ms |
20 〜50 |
|
| 1? | Opening time |
35 〜70 |
|
| 16 | Mechanical life |
times |
10000 |
|
17 |
Electrical life |
E2 class |
|
|
18 |
Allowed cumulative wearing thickness of moving contact and fixed contact | mm |
3 |
|
19 |
Clearance between open contacts | mm |
13±1 |
|
20 |
Over travel | mm |
3±1 |
|
No |
Item |
Unit |
Value |
|
21 |
Average closing speed |
m/s |
0.6〜1.0 |
|
22 |
Average opening speed |
m/s |
0.9〜1.7 |
|
23 |
Rated voltage of energy storage motor | V |
DC 220/DC110 |
|
24 |
Power of energy storage motor | W |
90 |
|
25 |
Contact closing bounce time |
ms |
<2 |
|
26 |
Three phase opening and closing asynchronism |
ms |
<2 |
| 27 | Each phase conductive circuit resistance |
uQ |
<45(630A); <35(1250A) |
| 28 | Contacts pressure | N |
3100 〜3″。 |
| 29 | Charging time | s |
<15 |
General Structure Drawing and Installation (unit: mm)


|
A |
B |
C |
|
210 |
550 |
901 |
|
230 |
600 |
941 |
|
275 |
650 |
1031 |
Product detail pictures:

Related Product Guide:
Sticking for the belief of "Creating items of top of the range and creating buddies with people today from all over the world", we normally put the interest of shoppers in the first place for Wholesale Parts Of Vacuum Circuit Breaker - VSG-24 Series Indoor High Voltage Vacuum Circuit Breaker – Ghorit, The product will supply to all over the world, such as: belarus, Gabon, Kenya, We are looking forward to cooperating closely with you to our mutual benefits and top development. We guaranteed quality, if customers were not satisfied with the products' quality, you can return within 7days with their original states.
By Sabina from Austria - 2018.10.31 10:02
It is a very good, very rare business partners, looking forward to the next more perfect cooperation!
By trameka milhouse from Hongkong - 2017.12.19 11:10
-
Factory Price Isolate Switch - FZW32-24 Series...
-
Best quality Indoor Load Break Switch - FZW32-...
-
Super Purchasing for Vcb Vacuum Circuit Breaker...
-
Cheapest Factory Vi - GHV-12G/630 Circuit Brea...
-
China Gold Supplier for Discnnector - GHV-12G/...
-
China wholesale Reclosure - GHV-12G/630 Circui...